Page view 51
Height: 200 cm (minimum room height without
steam condenser)
260 cm (minimum room height with steam
condenser)
Width: 90 cm
Depth: 75 cm
Weight (net): approx. 505 kg
Operating weight: approx. 665 kg
Voltage: see data plate
Rated load: see data plate
Fuse rating: see data plate
Compressed air connection: 600 kPa (6.0 bar) required for steam
operation
Steam connection (with electric TA): 250 - 1000 kPa (2.5 - 10 bar) / 140 - 180 °C
Steam connection (with steam TA): 250 - 600 kPa* (2.5 - 6 bar) / 140 -164 °C
Water pressure (flow rate): 200 -1000 kPa (2 - 10 bar) pressure
Hot, cold and de-ionised (AD) water: up to max. 70 °C
Ambient temperature from 5 °C to 40 °C
Altitude Max. 1500 m
#
Noise level in dB (A):
Sound level LpA for the cleaning cycle: <70
for the drying cycle: <70
Test marks: VDE, interference suppression, DVGW
! mark: MPG-Guidelines 93/42/EWG, Class IIa
*) if the steam pressure lies between 250 - 300 kPa (2.5 – 3.0 bar) the steam
drying unit (TA) will only reach a max. drying temperature of 90 - 100 °C.
#
If installed at altitudes above 1500 m the boiling point of the suds solution will be
lower. Disinfecting temperature parameters should be lowered and the holding
time increased (A
0
value).