HUMIDITY TRANSDUCER SPECIFICATIONS
Accuracy*: ± 2% / ±3% RH
Range: 0-100% RH
Hysteresis: ± 1%
Supply Voltage: 12-40 VDC
12-35 VAC (VDC output units only)
Compensated Temp Range: -30°F to 130°F (-35°C to 55°C)
Load Impedance: 3K ohms max. at 40 VDC (mA output units)
1K ohms min. (VDC output units)
* Includes non-linearilty and non-repeatability
Inspection
Requirements
For Additional Information See HU-226 Data Sheet
INSTALLATION
8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
Model HU-226
Technical Information
TI.226-02
TEMP / HUMIDITY TRANSDUCER
Inspect the package for damage. If damaged, notify the appropriate
carrier immediately. If undamaged, open the package and inspect
the device for obvious damage. Return damaged products.
• Do not use on oxygen service, in an explosive/hazardous
environment, or with flammable/combustible media.
• Disconnect power supply before installation to prevent
electrical shock and equipment damage.
• Make all connections in accordance with the job wiring diagram
and in accordance with national and local electrical codes. Use
copper conductors only.
• Use electrostatic discharge precautions (e.g., use of wrist straps)
during installation and wiring to prevent equipment damage.
• Avoid locations where severe shock or vibration, excessive
moisture or corrosive fumes are present. NEMA Type 4 housings
are intended for outdoor use primarily to provide a degree of
protection against wind-blown dust, rain, and hose-directed water.
• Do not exceed ratings of the device.
• Tools (not provided)
- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws
• Appropriate accessories
• Two #8 self-tapping mounting screws (not provided)
• Training: Installer must be a qualified, experienced technician
Model HU-226
Technical Information
TI.226-02
TEMP / HUMIDITY TRANSDUCER
Page 4 of 4
CHECKOUT DIMENSIONAL DATA
CALIBRATION
1. Verify that the unit is mounted in the correct position.
2. Verify appropriate input signal and supply voltage.
3. Verify appropriate configuration range.
CAUTION: Never connect 120 VAC to these transducers.
Never connect AC voltage to a unit intended for DC supply.
Transducer
Operation
Calibration of HU-226 mA/VDC Humidity Transducer
Field calibration instructions are provided with the following
precautions and advice:
1. Do not verify comparative RH with a sling Psychrometer.
There are far too many variables which induce errors into
this process. New HU-226 RH transducers are already
supplied with calibration.
2. Recalibration must be done in a controlled environment.
Relative humidity must be held stable while making any
adjustment.
3. Verify the output from the device directly with calibrated
instrumentation and verify the RH with calibrated instrumen-
tation, (NOT A CONTROLLER OUTPUT). With the correct
power applied and only a meter connected to the output of
the transducer, ensure that the output is proportional to the
true RH.
4. A) SINGLE POINT CALIBRATION:
[NOTE: SELECT EITHER OPTION 1 OR OPTION 2,
BUT NOT BOTH.]
Option 1. Select a controlled humidity environment
between 10 & 40% R.H. Insure humidity
is stable and adjust zero trimmer (Z).
Option 2. Select a controlled humidity environment
between 40 & 70% R.H. Insure humidity
is stable and adjust span trimmer (S).
B) TWO-POINT CALIBRATION: Select a controlled
humidity environment between 10 & 40% RH Insure
humidity is stable and adjust zero trimmer (Z). Then
select a controlled humidity environment between
70 & 75% RH. Insure humidity is stable and then
adjust span trimmer (S).
All units are factory calibrated to meet or exceed published
specifications. If field adjustment is necessary, follow the
instructions below.
MAINTENANCE
Regular maintenance of the total system is recommended to
assure sustained optimum performance.
FIELD REPAIR
None. Replace with a functional unit.
WARRANTY
See Data Sheet for additional information.
Figure 6 - HU-226 Humidity Transducer Dimensions shown in inches and
millimeters (mm).
For Technical / Application Assistance call your nearest office
8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
EUROPE
Baird House, Units 6 & 7
Dudley Innovation Centre
Pensnett Estate • Kingswinford
West Midlands • DY6 8XZ
United Kingdom
01384-271113 • Fax 01384-271114
AUSTRALIA
4 Arminger Court, Unit 2
Holden Hill • S.A. 5088
Australia
08-8359-4333 • Fax 08-8395-4433
CANADA
155 McIntosh Drive, Unit 5
Markham • Ontario • L3R 0N6
Canada
905-474-9215 • Fax 905-474-0876
ASIA
No. 22 Lorong 21A Geylang #11-02
Prosper Industrial Building
Singapore • 388421
656-3927273 • Fax 656-3927276
MAMAC Systems, Inc., reserves the right to change any specifications without
notice to improve performance, reliability, or function of our products.
NOTE: The HU-226 is a highly accurate device. For
applications requiring a high degree of accuracy, the use of
laboratory-quality meters and gauges are recommended.
RoHS
RoHS
HU-226
Duct Mount
THERMISTOR SENSOR SPECIFICATIONS
Interchangeability: ± 0.2°C
Heat Dissipation: 3.0 mW/°C
R/T Characteristics: Refer to TI.700-11 (See Temperature Sensor section)
Operating Temp Range: -30°F to 130°F (-35°C to 55°C)
Conformance: EMC Standards EN50082-1(1992)
EN55014(1993)/EN60730-1(1992)
PLATINUM RTD SENSOR SPECIFICATIONS
Accuracy: 0.12% at 0°C
Resistance: 100 or 1,000 ohm at 0°C
Standard: DIN 43760
Heat Dissipation: 3.0 mW/°C
R/T Characteristics: Refer to TI.700-11 (See Temperature Sensor section)
Conformance: EMC Standards EN50082-1(1992)
EN55014(1993)/EN60730-1(1992)
GENERAL SPECIFICATIONS
Environmental: 10-90%RH Non-Condensing
Enclosure: 18 Ga C.R. Steel NEMA 4 (IP-65)
Finish: Baked on enamel - PMS2GR88B
Termination: Unpluggable screw terminal block
Wire Size: 12 Ga maximum
Weight: Duct Mount: 1.0 lbs. (.45 kg)
TEMP SENSOR
ACCURACY
(4-20 mA 2-wire)
(0-5 VDC/0-10 VDC
field selectable)
mA
VDC
Ex: HU-226-2-mA-3 - Temp/Humidity
Transducer, ±2%RH accuracy with 4-20
mA output and 1,000-ohm Platinum RTD.
For Resistance vs. Temperature Tables,
please refer to TI.700.11
OUTPUT
± 2%
ORDERING INFORMATION - HU-226-
± 3%
1
2
3
4
5
7
8
10
12
13
14
15
17
18
21
100 ohm Platinum RTD
1,000 ohm Nickel RTD
(5,000 PPM)
1,000 ohm Platinum RTD
1,000 ohm Nickel RTD
(6,000 PPM)
1,000 ohm Balco RTD
10,000 ohm NTC Thermistor
(Type III)
10,000 ohm NTC Thermistor
(Carel)
3,000 ohm NTC Thermistor
10,000 ohm NTC Thermistor
(Type II)
5,000 ohm NTC Thermistor
1,035 ohm Silicon PTC
100,000 ohm NTC Thermistor
20,000 ohm NTC Thermistor
2,252 ohm NTC Thermistor
1,800 ohm NTC Thermistor
Operating Temp Range: -30°F to 130°F (-35°C to 55°C)
TI.226-02
Warning:
Caution:
4.00”
(101.6)
2.63”
(66.8)
3.25”
(82.55)
2.81”
(71.37)
2.81”
(71.37)
5.00”
(127.0)
5.63”
(143.0)
.50”
(12.7)
2.00”
(50.8)
6.00”
(152.4)